range | TeSys |
---|---|
range of product | TeSys Giga |
product or component type | Contactor |
device short name | LC1G |
contactor application | Power switchingMotor control |
utilisation category | AC-1AC-3AC-3eAC-4AC-5aAC-5bAC-6aAC-6bAC-8bAC-8aDC-1DC-3DC-5 |
poles description | 3P |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<= 300 V DC |
[Ie] rated operational current | 700 A (at <40 °C) at 440 V AC-1500 A (at <40 °C) at 440 V AC-3 |
[Uc] control circuit voltage | 200...500 V AC/DC 50/60 Hz |
colour | Dark grey |
[Uimp] rated impulse withstand voltage | 8 kV |
overvoltage category | III |
rated breaking capacity | 4370 A at 440 V |
[Icw] rated short-time withstand current | 4.0 kA - 10 s2.8 kA - 30 s2.2 kA - 1 min1.5 kA - 3 min1.2 kA - 10 min |
associated fuse rating | 500 A aM at 440 V400 A aM at 690 V800 A gL at 690 V |
average impedance | 0.00008 Ohm |
[Ui] rated insulation voltage | 1000 V |
power dissipation per pole | 40 W AC-1 - Ith 700 A20 W AC-3 - Ith 500 A |
compatibility code | LC1G |
pole contact composition | 3 NO |
auxiliary contact composition | 1 NO + 1 NC |
network frequency | 50/60 Hz16.67...400 Hz |
motor power kW | 147 kW at 230 V AC 50/60 Hz (AC-3e)250 kW at 400 V AC 50/60 Hz (AC-3e)250 kW at 415 V AC 50/60 Hz (AC-3e)280 kW at 440 V AC 50/60 Hz (AC-3e)315 kW at 500 V AC 50/60 Hz (AC-3e)355 kW at 690 V AC 50/60 Hz (AC-3e)335 kW at 1000 V AC 50/60 Hz (AC-3e)160 kW at 230 V AC 50/60 Hz (AC-3)250 kW at 400 V AC 50/60 Hz (AC-3)250 kW at 415 V AC 50/60 Hz (AC-3)315 kW at 440 V AC 50/60 Hz (AC-3)355 kW at 500 V AC 50/60 Hz (AC-3)355 kW at 690 V AC 50/60 Hz (AC-3)335 kW at 1000 V AC 50/60 Hz (AC-3)150 kW at 230 V AC 50/60 Hz (AC-4)250 kW at 400 V AC 50/60 Hz (AC-4)250 kW at 415 V AC 50/60 Hz (AC-4)295 kW at 440 V AC 50/60 Hz (AC-4)295 kW at 500 V AC 50/60 Hz (AC-4)355 kW at 690 V AC 50/60 Hz (AC-4)280 kW at 1000 V AC 50/60 Hz (AC-4) |
motor power hp | 150 hp at 200/208 V 60 Hz200 hp at 230/240 V 60 Hz400 hp at 460/480 V 60 Hz450 hp at 575/600 V 60 Hz |
control circuit voltage limits | Operational: 0.8...1.1 Uc AC/DC (at 60 °C)Drop-out: 0.1...0.45 Uc AC/DC (at 60 °C) |
coil technology | Built-in bidirectional peak limiting |
mechanical durability | 5 Mcycles8 Mcycles with sub-assembly substitution |
inrush power in VA (50/60 Hz, AC) | 535 VA |
inrush power in W (DC) | 300 W |
hold-in power consumption in VA (50/60 Hz, AC) | 15.4 VA |
hold-in power consumption in W (DC) | 8.6 W |
operating time | 45...60 ms closing15...45 ms opening |
maximum operating rate | 300 cyc/h AC-1500 cyc/h AC-3500 cyc/h AC-3e150 cyc/h AC-4 |
connections - terminals | Power circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end |
connection pitch | 45 mm |
mounting support | Plate |
standards | EN/IEC 60947-4-1EN/IEC 60947-5-1UL 60947-4-1CSA C22.2 No 60947-4-1JIS C8201-4-1JIS C8201-5-1 |
Teknik özellikler bulunmuyor.